Downloading a Supervisory Application Design

The supervisory application design is downloaded to the LNS Server, and
optionally an SCH-10 module, using the following Load/Save tab.

To download the design into an LNS Server, and optionally a SCH-10 module,
follow these steps:

1. Select Local Server if you are running on the same PC with the LNS

Server; uncheck Local Server if you are running on a remote PC.

2. Select Network Attached if your PC is physically attached to the network;

uncheck Network Attached if your PC is not physically attached.

3. Select OnNet if your PC is attached, and you want the design to be

immediately downloaded to the SCH-10 module. Clear OnNet to store the
design only in the LNS database. The design will be downloaded to the
device the next time the LNS Server is OnNet.

4. Click the Open button. The available LNS network interfaces will be listed

in the Network Interfaces list.

5. Select a network interface in the Network Interfaces list to show all

available networks in the Networks list.

6. Select the network containing the SCH-10 device to be configured from the

Network

list. After a delay, the LonPoint Schedule Maker utility

determines the top-level subsystem of the selected network and displays it in
the Top Subsystem field. All the available SCH-10 devices in this
subsystem are listed in the SCH-10 Devices list. The LonPoint Schedule