Analog output – Echelon LonPoint Application and Plug-In User Manual

Page 69

Advertising
background image

The LonPoint Application and Plug-in Guide

7-3

Analog Output

This tab appears as follows:

This tab sets configuration properties that determine how the values received by
the input network variables are processed by the functional block and what
values are sent to the physical actuator. This tab allows you to set the following
fields:

Location

The location string for this analog output. This
property can be used to document the associated
actuator’s location within the plant so it can be easily
found. This field may contain up to 30 characters.
This value is not the device’s location property.

Invert

Inverts the value received on the Enable network
variable. If this option is selected, sending an Off
value to the Enable network variable will enable the
input.

Input Range

Defines the minimum and maximum input values
that correspond to the minimum and maximum
output values. If the input falls below the minimum,
the output is set to the minimum output value. If the
input exceeds that maximum, the output is set to the
maximum output value. If the Enabled option is not

Advertising