Processing parameters – Echelon LonPoint Application and Plug-In User Manual

Page 35

Advertising
background image

The LonPoint Application and Plug-in Guide

3-9

HOLD

Holds the current value of the Analog network
variable. Events are accumulated but the network
variable is not updated. The HOLD state does not apply
to the Repeating Count processing option. The Analog
network variable will continue to update if Repeating
Count is selected.

PAUSE

Disables event counting. The internal count value
and Analog network variable are not updated.

PRESET

Presets the counter to the value specified in the preset
value configuration property. The new value updates
the stored count in EEPROM.

Processing Parameters

This tab appears as follows:

This tab allows you to set several parameters relating to the processing option
selected in the Digital Input/Counter tab. The following parameters may be set
using this tab:

Count Repeat Value

This parameter is only used if the processing option is
set to Repeating Count. This integer value
determines the terminal count used for this
processing option (e.g. a value of 5 would result in a
count of 0, 1, 2, 3, 4, 0, 1, 2, …).