Output parameters – Echelon LonPoint Application and Plug-In User Manual

Page 46

Advertising
background image

4-8

Digital Output Functional Block

Output Parameters

This tab appears as follows:

This tab allows you to set options determining what information is sent to the
output. This tab contains the following fields:

Default Value

Determines the value that will be sent to the hardware if
the block is disabled or has detected a heartbeat failure.

Override Value

Indicates the output value that will be used if the
functional block is put into override. This value will be
inverted if the Output Invert option is selected.

Min On/Min Off

Indicates the minimum amount of time an On to Off
condition will be sent to the hardware digital output and
the Feedback network variable. If the Pulsed or One-
shot processing option is being used, there will always be
a delay of at least the Min Off time between pulses. To
modify the value in either of these fields, click the
associated button and enter appropriate values in the
Day

, Hour, Minute, Second, and Millisecond fields.