Output parameters – Echelon LonPoint Application and Plug-In User Manual

Page 62

Advertising
background image

6-6

Analog Input Functional Block

All fields on this tab will be disabled if the Translation Enabled option is not set
on the Analog Input tab.

Output Parameters

This tab appears as follows:

This tab determines how often data is sent on the Analog network variable and
the minimum, maximum, and override values. This tab contains the following
fields:

Minimum Value

The minimum value that will be sent by the output
network variable. If this limit is exceeded the output
will be clipped at this limit.

Maximum Value

The maximum value that will be sent by the output
network variable. If this limit is exceeded the output
will be clipped at this limit.

Send on Delta

The sensed value must change by at least this
amount before a new value is sent. A new value will
still be sent if the heartbeat time expires.

Override

The value that will be sent by the Analog output
network variable if this functional block is put into
override.