Digital output – Echelon LonPoint Application and Plug-In User Manual

Page 41

Advertising
background image

The LonPoint Application and Plug-in Guide

4-3

Digital Output

This tab appears as follows:

This tab displays the flow of information through the Digital Output functional
block. It contains the following fields:

Location

The location string for this digital output. This
property can be used to document the associated
actuator’s location within the plant so it can be easily
found. This field may contain up to 30 characters.
This value is separate from the LonPoint device’s
location property.

Digital Input Invert

Specifies whether or not the value of the Digital
network variable is inverted before it is processed.

Enable Invert

Specifies whether or not the value of the Enable
network variable is inverted before it is processed. If
not selected, an On value enables the output.

Output Invert

Specifies whether or not the value of the digital
output value is inverted before it is sent to the
attached hardware. This option does not apply to the
Feedback

output.