Echelon LonPoint Application and Plug-In User Manual

Page 23

Advertising
background image

The LonPoint Application and Plug-in Guide

2-5

the new values to be used for the delay. The valid
range for this value is from zero to 48 days, 23 hours,
59 minutes, 59 seconds, and 999 milliseconds.

Off Delay Time

Use this field with the Delayed Processing option.
This value determines the length of the delay in the
change from the on state to the off state. To change
the value, click the button to the right of the time
value to be changed and enter the new values to be
used for the delay. The valid range for this value is
from zero to 48 days, 23 hours, 59 minutes, 59
seconds, and 999 milliseconds.

Pulse Time

If you select either the Pulsed or the One-Shot
Processing

options, the Pulse Time field appears

in place of Off Delay Time. This value determines
the length of time the on state remains active. To
change the value, click the button to the right of
the time value to be changed and enter the new
values to be used for the pulse. The valid range for
this value is from zero to 48 days, 23 hours, 59
minutes, 59 seconds, and 999 milliseconds.

Override Value

Determines the value sent to the network via the
output network variable if the functional block is put
into override mode as described in the next section.

Heartbeat

Determines how often the functional block sends a
heartbeat over the network. The behavior of the
system in case of a missed heartbeat is determined by
the functional blocks which fail to receive the
heartbeat. Setting this property to 0 disables the
heartbeat for this functional block. Disabling the
heartbeat causes the output network variable to only
be transmitted in response to a changed input value.

Throttle

Limits how often data is sent over the network.
Setting this property to 0 disables throttling.

Advertising