Data Logger Functional Block

Changing Network Variable Types in Chapter 1. There are no restrictions on the
network variable types allowed.

Input Options

This tab appears as follows:

This tab contains the following fields:

Log Number

Specifies which log the data received on the
corresponding Data Input will be sent to. The log
may perform additional filtering as described in the
Input Limits

tab. This value must be an integer

from 0 to 3. Setting this value to 0 disables logging for
the corresponding input.

Timestamp

Specifies that a timestamp will be included with
every piece of data logged from the corresponding
Data Input.

Source Addr

Specifies that the Subnet/Node address of the device
that the data was received from will be included with
every piece of data logged from the corresponding
data input. See Tagnames, later in this chapter.

Max Storage Rate

Specifies the minimum amount of time between
logging data. This allows you to take data samples at