The analog input functional block – Echelon LonPoint Application and Plug-In User Manual

Page 58

Advertising
background image

6-2

Analog Input Functional Block

The Analog Input Functional Block

The Analog Input functional block measures the voltage, current, or resistance
of a hardware transducer. This value is then translated into an appropriate
value to send on the Analog output network variable. For example, a
temperature transducer might return a value of 10,000 to 15,000 ohms. The
Analog Input functional block translates this raw value into the appropriate
temperature value using a translation table. The following figure and table
summarizes the output of the Analog Input functional block:

Output Network Variables

Default name

Default type

Description

Analog

SNVT_temp_f

(changeable)

The Analog output network
variable driven by the sensor.

Configuring an Analog Input with the LonPoint Plug-in

Right-click an Analog Input functional block and select Configure from the
shortcut menu to open the LonPoint Plug-in. The Analog Input window of the
LonPoint Plug-in contains the following tabs: Analog Input, Translation,
Output Parameters

, and Status.