The LonPoint Application and Plug-in Guide

3-11

Input/Counter software automatically linearly interpolates to determine
translation values that lie between defined input/output pairs.

The table must contain at least two input/output pairs and may contain as many
as twenty.

The only constraint on the Measured Value column is that the entries increase in
value. To mark the end of the table, enter a measured value less than the
preceding one.

Click the Save button to save translation table data into a tab-delimited text file.
Click the Load button to load data from a tab-delimited text file into a translation
table. Use these functions to save and reuse commonly used translation tables for
your hardware inputs. You can also use custom LonMaker shapes to save
frequently used configurations.

Output Parameters

This tab appears as follows:

This tab allows you to determine parameters for the output network variables on
the Digital Input/Counter functional block. Not all of the parameters are
configurable for every processing option.

Offset

This parameter is only used if the Frequency
processing option is being used. This value is added
to the sensed reading prior to sending the reading on