Programid, Selfdocumentation, State – Echelon OpenLNS User Manual

Page 124

Advertising
background image

OpenLNS Programmer's Reference

87

127 lcaLNSNodePriorityMax

Represents the maximum number of

priority slots on any LonTalk

channel. Do not set the MaxPriority

property to a value greater than this.
255 lcaLNSNodePriorityAny
The Object Server will assign the

AppDevice

object the next available,

or least used, priority slot on the

channel.

object

The

AppDevice

object to be acted on.

Data Type

Integer.

Read/Write

Read/write.

Added to API

Prior to LNS Release 3.0.

ProgramId

Summary

Stores the program ID for the application device. Every

LonMark compliant LONWORKS application device uses a

unique, 16 digit, hexadecimal standard program ID that uses

the following format:

FM:MM:MM:CC:CC:UU:TT:NN
See the Devices Interfaces section in Chapter 6 of the

OpenLNS Programmer’s Guide for a description of the format

used to display program IDs.

Availability

Local, full, and lightweight clients.

Syntax

programIdValue = object.ProgramId

Element

Description

programIdValue

The program ID value of the object.

object

The object to be acted on.

Data Type

String.

Read/Write

Read only.

Added to API

Prior to LNS Release 3.0.

SelfDocumentation

Summary

Stores the self-documentation string of the application

device.
The length of the string is not provided as a separate

property. To get the length, get the descriptionString, and

calculate the length from it. Note that this property returns

only the user portion (which follows the LonMark portion, if

any) of the self-documentation string

Advertising