168

Once the implementation type is known, a client can retrieve

the appropriate addressing information for the configuration

property by reading either the ConfigNvIndex property (for

NV-based CPs), or the ConfigFileType and ConfigFileOffset

properties (for file-based CPs).
This information is useful for tools that need to access

configuration property values when OpenLNS is not

available. For example, the SmartServer needs this

information to manage configuration property values when it

is running in standalone mode.
Notes: Modifying configuration property values without

OpenLNS is typically nor recoemmnded because it causes the

application device and the OpenLNS database to lose

synchronization.
This property is not currently available from within a

DeviceTemplate object; therefore, it will throw a

LCA, #38

LCA_APP_DEVICE_REQUIRED

exception when accessed.

Availability

Local, full, and lightweight clients.

Syntax

cpType = cpObject.ImplementationType

Element

Description

cpType

The configuration property’s

implementation type.
The possible values for this property,

which are stored in the

ConstImplementationTypes constant,

are as follows

:

1 lcaImplementedByNetworkVariable
The configuration property is

implemented by a configuration

network variable. To determine the

index of the configuration variable,

read the ConfigNvIndex property of

the ConfigProperty

object.

2 lcaImplementedByConfigFile
The configuration property is

implemented by a configuration value

file. To determine the type and offset

into the configuration value file, read

the ConfigFileType and

ConfigFileOffset properties of the

ConfigProperty

object.

cpObject

The

ConfigProperty

object to be acted

on.

Data Type

Short.

Read/Write

Read only.

Advertising