Echelon OpenLNS User Manual

Page 91

Advertising
background image

OpenLNS Programmer's Reference

54

2 lcaTestResultCommNeuronId
The OpenLNS Server was unable to

communicate with the device using Neuron

ID addressing. Because the device has not

been added or defined, the OpenLNS Server

could not test the device using subnet/node

ID addressing. The OpenLNS Server might

not be attached to the network, the Network

Service Device might be unconfigured, the

target device might not be attached to the

network, the target device may be powered

off, or the target device may be faulty.
3

lcaTestResultCommNeuronIdVerified
The OpenLNS Server was able to

communicate with the device using

subnet/node addressing, but could not

communicate with the device using Neuron

ID addressing. However, through the use of

subnet/node addressed messages, the

OpenLNS Server has verified that the device

contains the expected Neuron ID. This

might be caused by intermittent device or

channel failures. You may want to retry this

method to see if the error persists.
4 lcaTestResultCommSnode
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. The OpenLNS Server was

unable to verify whether the device has been

configured with the proper

domain/subnet/node address. The device

may have reconfigured itself, the device may

have been reconfigured by another network

management tool, or the device may be

faulty. The device may be restored using the

Commission method.
5 lcaTestResultSnodeVerified
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. However, through the use of

Neuron ID addressed messages, The

OpenLNS Server has verified that the device

contains the expected subnet/node address.

This error can occur if the target device is in

an unconfigured state. The device may need