Bufferconfiguration – Echelon OpenLNS User Manual

Page 141

Advertising
background image

OpenLNS Programmer's Reference

104

ConstApplicationState

constant, are as

follows:

0 LcaApplOnline

The application is currently executing.
1 LcaApplOffline

The application is not currently

executing.

appObject

The

Application

object to be acted on.

Data Type

Integer.

Read/Write

Read only.

Added to API

LNS Release 3.0.

BufferConfiguration

A BufferConfiguration object contains the communication buffer parameters for a

RouterSide

object. Changes made to the buffer count and size properties are temporary. To save

changes to these properties and propagate the new values on the network, the

BufferConfiguration

property of the

RouterSide

object must be set with the modified

BufferConfiguration object.
The maximum buffer size for a router side is determined when the router's external interface

file is imported. No changes may be made to the

BufferConfiguration

property of the

RouterSide

object that would cause the total memory usage value to be exceeded. You can

specify a different external interface file that allows for greater memory for a router if you

want to change this value. The external interface file for a router must be specified before

the router is commissioned; therefore, you must follow this procedure to do so:

1. Use the Decommission method on the router that needs to be modified.
2. Use the AddEx method to add a replacement router object to the OpenLNS database.

Use lcaRouterFlagNoSplit (0) as the flags option when you call the method.

3. Import the external interface file that will be used by the router. Note that the

LonWorks\Import\Router.xif is the correct external interface file to use for all LonPoint

routers, and for any routers based on the RTR-10 SIM Module.

4. Set the ProgramId property of each RouterSide object of the replacement router to match

that of the external interface file used by that type of router. This should be the external

interface file imported in Step 3.

5. Use the Commission method on the replacement router. Once you have commissioned

the router, you can set the properties of the

BufferConfiguration

object to use the

additional memory allowed by the new external interface file.

6. Remove the old router.
The following table summarizes the BufferConfiguration object.

Description

Contains the communication buffer parameters for a

RouterSide

object.

Added to API

Prior to LNS Release 3.0.

Accessed Through

RouterSide

object

.