OpenLNS Programmer's Reference

934

10 lcaTestResultNoNeuronId
The device has not been assigned a Neuron

ID.
11 lcaTestResultMismatchProgramId
The OpenLNS Server was able to

communicate with the device using both

Neuron ID and subnet/node addressing.

However, the device does not contain the

expected program ID. The device’s program

ID may have been changed by its

application program. Host devices can

modify the program ID of their attached

network interface. The device should be

Removed and Added.
12

lcaTestResultCommSnodeNotVerified
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. The OpenLNS Server did not

attempt to verify that the device has been

configured with the proper

domain/subnet/node address because the

device is currently authenticated, and

reading the address would result in

transmitting the key over the network. The

device may have reconfigured itself, the

device may have been reconfigured by

another network management tool, or the

device may be faulty. The device may be

restored using the Commission method.
13 lcaTestResultAuthEnabled
The OpenLNS Server was able to

communicate with the device using both

Neuron ID addressing and subnet/node

addressing. However, the device has

network management authentication

enabled despite the fact that the device’s

AuthenticationEnabled property is set to

FALSE. The device may have enabled

network management authentication itself,

the device may have been reconfigured by

another network management tool, or the

device may be faulty. It may be possible to

restore the device using the Commission

method.
14 lcaTestResultAuthDisabled
The OpenLNS Server was able to

Advertising