OpenLNS Programmer's Reference

596

object’s DsPollInterval property. An exception will be raised

if you attempt to do so.
The System object's DsPollInterval property sets the default

value which is applied when a NetworkVariable object's

DsPollInterval property is left unspecified. Once an

application has explicitly set the value of the DsPollInterval

property of the System object, it will not be reverted back to

the default value by OpenLNS, and must be maintained

manually from that point on.
Invoke the DsSaveOptions to save the property value into the

persistent database.
This property applies only to points monitored and controlled

using single-point monitoring. If you are using monitor set

monitoring, use the PollInterval property.

Availability

Local, full, and lightweight clients.

Syntax

intervalValue = object.DsPollInterval

Element

Description

intervalValue Poll or throttle interval, in tenths of a

second.

The allowed range is 0 to

33554431 (0x01FFFFFF). This

maximum value corresponds to a time of

approximately 38.8 days. The default

value is 10 (one second) for System

.DsPollInterval.
The system's current DsPollInterval

value establishes the default that will be

used by newly created NetworkVariable

objects whose DsPollInterval value is

left unspecified.

object

The

NetworkVariable

object to be acted

on.

Data Type

Integer.

Read/Write

Read/write.

Added to API

Prior to LNS Release 3.0.