OpenLNS Programmer's Reference

56

You can resolve this problem by physically

removing the obsolete device.
9 lcaTestResultMismatchSnode
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using its subnet/node

addressing. Through the use of Neuron ID

addressed messages, the NSS has found that

the subnet/node address configured in the

device does not match the database. This

result will be returned if the device’s domain

address has not been configured.
10 lcaTestResultNoNeuronId
The device has not been assigned a Neuron

ID.
11 lcaTestResultMismatchProgramId
The OpenLNS Server was able to

communicate with the device using both

Neuron ID and subnet/node addressing.

However, the device does not contain the

expected program ID. The device’s program

ID may have been changed by its application

program. Host devices can modify the

program ID of their attached network

interface. The device should be Removed

and Added.
12

lcaTestResultCommSnodeNotVerified
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. The OpenLNS Server did not

attempt to verify that the device has been

configured with the proper

domain/subnet/node address because the

device is currently authenticated, and

reading the address would result in

transmitting the key over the network. The

device may have reconfigured itself, the

device may have been reconfigured by

another network management tool, or the

device may be faulty. The device may be

restored using the Commission method.
13 lcaTestResultAuthEnabled
The OpenLNS Server was able to

communicate with the device using both