8 measures to prevent accidents – BINDER FDL 115 User Manual

Page 16

Advertising
background image

FDL (E2.1) 02/2015

page 16/75

1.8 Measures to prevent accidents

During drying of fluid paints, flammable solvent/air mixtures can form and ignite.
The manufacturer took the following measures to prevent ignition and explosions:

Indications on the type plate
See operating manual chap. 1.4

Operating manual
An operating manual is available for each safety drying oven.
A diagram in the operating manual (chap. 2.3) indicates the maximum permissible solvent quantities

for various operating states.
The operating manual asks the operator of the safety drying oven to set up an instruction on the per-

missible loading quantity.

Maximum temperatures and maximum permissible steam concentration
By means of the diagram “Highest permissible solvent quantity”, which is included in the operating

manual chap. 2.3 and applied on the front of the safety drying oven, the operator must adapt the dry-

ing temperature to the maximum solvent quantity arising.
When using nitro-cellulose lacquers or nitro combination lacquers, the diagram ”Highest permissible

solvent quantity” specifies a limit temperature of max. 130 °C/ 266 °F, which must not be exceeded.

(In this context, all paints containing more than 5 % nitro-cellulose relative to the non-volatile contents

are regarded as nitro-cellulose lacquers and nitro-combination lacquers).
A gas-tight separation between the drying chamber and the heating chamber is not necessary since

there is an effective forced air motion in the entire steam room.

Throttle valves
No throttle valves are used, i.e., the full air change occurs permanently.

Protecting the heating surfaces against dripping
All heating elements are protected against lacquer dripping and direct contact with lacquer coatings.

Heat insulation
All heat insulation is sealed against penetration by lacquer vapors from the outside with high tempera-

ture-resistant and ageing-resistant sealant.
The insulation material consists of non-combustible mineral wool (class A1 according to DIN 4102-

1:1998).

Overtemperature monitoring
The safety drying oven is equipped with a temperature display, which can be read from outside.
A built-in additional temperature safety device can turn off the heating and is functionally independent

of the main controller. When turning off the unit, the forced convection and the control equipment’s

function are maintained.
Visual (red indicator light) and audible (buzzer) signals indicate temperature exceeding.

Monitoring the stream of exhaust air during prepurge
The unit complies with the requirements on monitoring the pressure switch according to EN

1539:2009 and EN ISO 13849:2008.
The fan only turns on after pressing pushbutton “START” (4).
After approx. 2 minutes of prepurge with monitoring the stream of exhaust air the heating turns on.

Door switch
When opening the door, fan and heating turn off. To restart the drying process new prepurge is re-

quired.