Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual
Page 76
Using HPI-B
System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide
76
Cooling_DeactOnUpperNonRecov
erTemp
<valid only for C2000 systems>
“1”
Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 shelf.
Cooling_FanMinimumLevel
“12|15”
Default fan speed in %.
12 - default value for C2000 shelfs.
15 - default value for the other shelfs.
Cooling_InletOutletLowerTemp
erature
“20”
Lower temperature point for inlet/outlet
control
Cooling_InletOutletUpperTemp
erature
“40”
Upper temperature point
Cooling_InletOutletLowerSetP
oint
“10”
Set point at upper temperature
Cooling_InletOutletUpperSetP
oint
“25”
Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.
Cooling_InltOutltMinimumSens
orTemperature
“18”
Below this inlet temperature the
inlet/outlet related control is disabled
Cooling_BoardSetPointOffset
“0”
The temperature difference to the
upper-non-critical Threshold of a blade.
E. g. threshold at 85, a 5 would result in
holding the temperature at 80. Allowed
range is 0 to 5
Cooling_BoardConsiderHystere
sis
“0”
“1” subtracts a hysteresis from the set
point
Cooling_BoardMinNumControlle
d
“10”
Minimum number of sensors to be
polled after a temperature event
Cooling_BoardMaxNumControlle
d
“10”
Maximum number of sensors to be
polled Both should not be changed
Table 4-39 Parameters of Cooling System (continued)
Parameter Name
Default Value
Description