Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual

Page 76

Advertising
background image

Using HPI-B

System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide

76

Cooling_DeactOnUpperNonRecov

erTemp

<valid only for C2000 systems>

“1”

Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 shelf.

Cooling_FanMinimumLevel

“12|15”

Default fan speed in %.
12 - default value for C2000 shelfs.
15 - default value for the other shelfs.

Cooling_InletOutletLowerTemp

erature

“20”

Lower temperature point for inlet/outlet
control

Cooling_InletOutletUpperTemp

erature

“40”

Upper temperature point

Cooling_InletOutletLowerSetP

oint

“10”

Set point at upper temperature

Cooling_InletOutletUpperSetP

oint

“25”

Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.

Cooling_InltOutltMinimumSens

orTemperature

“18”

Below this inlet temperature the
inlet/outlet related control is disabled

Cooling_BoardSetPointOffset

“0”

The temperature difference to the
upper-non-critical Threshold of a blade.
E. g. threshold at 85, a 5 would result in
holding the temperature at 80. Allowed
range is 0 to 5

Cooling_BoardConsiderHystere

sis

“0”

“1” subtracts a hysteresis from the set
point

Cooling_BoardMinNumControlle

d

“10”

Minimum number of sensors to be
polled after a temperature event

Cooling_BoardMaxNumControlle

d

“10”

Maximum number of sensors to be
polled Both should not be changed

Table 4-39 Parameters of Cooling System (continued)

Parameter Name

Default Value

Description