Table 4-40, Hpi-b daemon log messages, Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual

Page 77

Advertising
background image

Using HPI-B

System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide

77

Once enabled, the HPI-B daemon log files will have the following log messages:

04:14:21.732 <debug> {ipmicooling}: 9a.0/0/af: sp=85.0 y=84.5

xd=0.04 xdi=-484.7 xdp=0.008 u=14.3

04:14:21.733 <debug> {ipmicooling}: New fan level 14 driven by

9a.0/0/af

04:14:26.698 <debug> {ipmicooling}: 9a.0/0/af: sp=85.0 y=84.6

xd=0.00 xdi=-484.6 xdp=-0.008 u=14.7

04:14:26.699 <debug> {ipmicooling}: New fan level 15 driven by

9a.0/0/af

04:14:31.699 <debug> {ipmicooling}: 9a.0/0/af: sp=85.0 y=84.5

xd=0.05 xdi=-484.5 xdp=0.009 u=14.2

04:14:21.733 <debug> {ipmicooling}: New fan level 14 driven by

9a.0/0/af

Following table describes the way to interpret these log messages.

Cooling_FanConsiderFailureEv

ent

“0”

A “1” treats a fan, which had sent a lower
critical event, as broken and would
increase the speed of the remaining fans
accordingly. Default controls the speed
related to measured temperatures only.

Table 4-40 HPI-B daemon Log Messages

Code in log message

Name, Description

sp

Set Point for the control

y

Filtered value of read sensor

u

Calculated speed in %

xd

Difference of sp - y - tolerance

xdi

Integral

Table 4-39 Parameters of Cooling System (continued)

Parameter Name

Default Value

Description