5-10

BE1-87T Test Procedures

9171300990 Rev V

If there are more than three inputs (as in some single-phase units), continue substituting every

higher-numbered input for Input 2, each time comparing the input under test against Input 1 as

in Steps 6 and 7.

Step 9. Three-Phase Units Only: Repeat Steps 6, 7 and 8 for phases B and C. (Refer to Figures 5-1

through 5-4, as appropriate, for the terminal numbers of the phase B and C inputs.)

Table 5-1. Restrained Pickup Test: 5 A, 50 or 60 Hz

Input 1, Tap = 2.0

Input 2, Tap = 3.8

Increasing Input 1 Decreasing Input 2

% Slope Amperes X Tap

Amperes X Tap

Trip Amperes

Trip Amperes

15

2.0

1

3.8

1

2.70 ±0.26

2.47 ±0.25

15

4.0

2

7.6

2

4.71 ±0.38

6.27 ±0.48

15

6.0

3

11.4

3

7.06 ±0.52

9.69 ±0.68

15

10.0

5

19.0

5

11.76 ±0.81

16.15 ±1.07

25

2.0

1

3.8

1

2.70 ±0.26

2.47 ±0.25

25

4.0

2

7.6

2

5.33 ±0.42

5.70 ±0.44

25

6.0

3

11.4

3

8.00 ±0.58

8.55 ±0.61

25

10.0

5

19.0

5

13.33 ±0.90

14.25 ±0.96

50

2.0

1

3.8

1

4.00 ±0.34

1.90 ±0.21

50

4.0

2

7.6

2

8.00 ±0.58

3.80 ±0.33

50

6.0

3

11.4

3

12.00 ±0.82

5.70 ±0.44

50

10.0

5

19.0

5

20.00 ±1.30

9.50 ±0.67

30

2.0

1

3.8

1

2.86 ±0.27

2.47 ±0.25

30

6.0

3

11.4

3

8.57 ±0.61

7.98 ±0.58

35

2.0

1

3.8

1

3.08 ±0.28

2.47 ±0.25

35

6.0

3

11.4

3

9.23 ±0.65

7.41 ±0.54

40

2.0

1

3.8

1

3.33 ±0.30

2.28 ±0.24

40

6.0

3

11.4

3

10.00 ±0.70

6.84 ±0.51

60

2.0

1

3.8

1

5.00 ±0.40

1.52 ±0.19

60

6.0

3

11.4

3

15.00 ±1.00

4.56 ±0.37

Input (or Tap) Switch Verification

Each input is scaled using a combination of two rotary switches. Verify the switches as follows.

Step 1. Determine the Sensing Input Type (the first digit of the Style Number shown on the front panel):

A

Single-phase, two inputs

B

Single-phase, three inputs

C

Single-phase, four inputs

D

Single-phase, five inputs

E

Three-phase, two inputs each phase

G

Three-phase, three inputs each phase

Step 2. Connect the input being tested to the current source, as shown in the appropriate TEST

SETUP, Figures 5-1 through 5-4.