Unrestrained pickup verification, Unrestrained pickup verification -16, Table 5-6. input verification*: 1 a, 50 or 60 hz – Basler Electric BE1-87T User Manual

Page 112

Advertising
background image

5-16

BE1-87T Test Procedures

9171300990 Rev V

Step 2. Connect the input being tested to the current source as shown in the appropriate diagram,

Figures 5-1 through 5-4.

Step 3. Set the INPUT under test to the 0.78 tap position as shown in Table 5-6. Set the RESTRAINED

PICKUP LEVEL switch to position A (15%). Apply current to the input under test, increasing

the current until the

REST. TRIP LED lights. At this point, the input current should be 0.273 A

±

6%

±

20 mA.

Step 4. Repeat Step 3 for the additional tap positions shown in Table 5-6. This verifies the accuracy of

all the binary combinations of the rotary switches.

Step 5. Test the other inputs by reconnecting to the next pair of terminals for your relay and repeating

Steps 3 and 4. (The successful completion of these tests will verify the electrical integrity of all

the tap switches.)

Table 5-6. Input Verification*: 1 A, 50 or 60 Hz

Tap† Position

Input Current Range

at Pickup

0.78

0.24 - 0.31 A

0.86

0.26 - 0.34 A

1.28

0.40 - 0.49 A

1.56

0.49 - 0.60 A

*

Pickup occurs at 0.35 x Tap. See Figure 1-2.

† The setting of the upper and lower

INPUT switches of the input being

tested. (Reference Figures 2-1 to 2-4.)

Unrestrained Pickup Verification

Step 1. Set the INPUT 1 (tap) switches to the 2.0 A position. Connect the relay as appropriate (refer to

Figures 5-1 through 5-4, as appropriate) using terminals 11 & 13 (Input 1 for both single-phase

and three-phase units).

Step 2. Set the UNRESTRAINED PICKUP LEVEL switch to position A (6 X TAP). Increase the input

current until the

UNREST. TRIP LED lights (disregard the REST. TRIP LED). This should occur

at 2.4 A ±3% as indicated in Table 5-7.

Step 3. Repeat Step 2 using the other UNRESTRAINED PICKUP LEVEL switch positions given in

Table 5-7.

Step 4. For Three-Phase Units Only: Repeat Steps 1 through 3 for Phase B of input 1 (terminals 12 &

13) and Phase C of input 1 (terminals 14 & 13).

Table 5-7. Unrestrained Pickup Verification, 1 A, 50 or 60 Hz

Unrestrained

Pickup Level

Input 1 Tap

Position

Input Current at

Pickup ±3%

A (6 X TAP)

0.4

2.4 A

J (14 X TAP)

0.4

5.6 A

S (21 X TAP)

0.4

8.4 A