Figure 4-28. 30° phase shift compensation jumpers – Basler Electric BE1-87T User Manual

Page 68

Advertising
background image

4-26

BE1-87T Installation

9171300990 Rev V

Figure 4-28. 30° Phase Shift Compensation Jumpers


The transformer in the example shown in Figure 4-28 and 4-29 has a delta connection on the primary

winding. The currents in each winding of the delta are A, B and C respectively as reflected from the wye

connected secondary winding. The delta connection of the transformer windings causes the current

flowing in the phase leads connected to the delta winding to be A-B, B-C and C-A respectively. The CT

currents on the wye side must be combined similarly to provide A-B, B-C and C-A to compensate. This is

done in Figure 4-28 by connecting the wye side CTs in delta such that the currents sent to the relay are

A-B, B-C and C-A. This is shown in Figure 4-29 by selecting phase compensation jumper position ∆2 for

the wye side input.

Advertising