Table 4-2. examples of suitable slope settings – Basler Electric BE1-87T User Manual

Page 83

Advertising
background image

9171300990 Rev V

BE1-87T Installation

4-41

)

42

.

2

(

4

23

)

3

6

.

10

(

35

3

+

+

=

S

= 38.8

Because the maximum saturation factor S

F

for this example is less than 0.5 (from Step 16), use

the next highest slope. Select position

F which = 40%.

For examples of suitable slope settings, see Table 4-2.

Table 4-2. Examples of Suitable Slope Settings

Maximum

Mismatch in %

(M

T

)

Current Rating of Power

Transformer in

Multiples of TAP (I

T

)

Recommended Minimum

RESTRAINED PICKUP

LEVEL Setting* (Slope)

2.5

1.5

15

2.5

2

20

5

2

25

10

1.5

30

12.5

1.5

35

15

1.5

40

15

2

45

15

2.5

50

20

1.5

55

20

2

60

* S

F

=V

B

/V

CE

If S

F

>0.5, set the RESTRAINED PICKUP LEVEL setting (slope) to S=60%.