Verify ct performance – Basler Electric BE1-87T User Manual

Page 87

Advertising
background image

9171300990 Rev V

BE1-87T Installation

4-45

Verify CT Performance

NOTE

This procedure uses the ANSI accuracy class method. See Appendix A,

Setting Note 7 for more information.

Step 12. Determine the maximum CT secondary fault current for external faults at F (I

F3

for three-phase,

and I

FG

for single-phase). Refer again to Figure 4-37 for this example:

HIGH

LOW

IF3

1916

60

=
= 32 A

IF3

10603

160

=
= 66 A

IFG

=
=

1171
60

19.5 A

IFG

=
=

11231

160

70 A

Step 13. Determine the worst case CT burden voltage for a three-phase fault (V

B3

).

For wye-connected CTs:

V

B3

= I

F3

(R

L

+ R

R

)

For delta-connected CTs, for three-phase fault:

V

B3

= I

F3

(R

W

+ 3R

L

+ 3R

R

)

Note that the wye connection produces a lower burden on the CTs (see Appendix A, Note 2).

Where:

I

F3

= determined in Step 12

R

L

= one-way lead resistance in ohms

R

W

= winding burden

R

R

= relay resistance in ohms (< 0.05 ohm)

Neglecting R

R

, use R

W

and R

L

from Figure 4-37:

HIGH

LOW

VB3

(32)(0.7)

=

= 22.4 V

VB3

(66)(0.7)

46.2 V

=
=

Step 14. Determine the worst case burden voltage for a line-to-ground fault (V

BG

).

For wye-connected CTs:

V

BG

= I

FG

(2R

L

+ R

R

)

Where:

I

FG

= determined in Step 12

R

L

= one-way lead resistance in ohms

R

R

= relay resistance in ohms

For delta-connected CTs:

V

BG

is a function of the proportion of positive-sequence to zero-sequence currents but may be

approximated by the same equation (for worst case).