Basler Electric BE1-87T User Manual

Page 85

Advertising
background image

9171300990 Rev V

BE1-87T Installation

4-43

Step 2. Determine the CT secondary current (I

S

):

HIGH

LOW

Step 3. Three-Phase Units Only: Adjust the phase compensation jumpers on Analog Board #2, shown

in Figure 2-4 (or use the procedure listed in

TESTING THREE-PHASE UNITS WITHOUT

CHANGING JUMPERS, in Section 5). Because of the grounded winding in this example, as

shown in Figure 4-37, the high-side and low-side zero-sequence currents must be canceled.

Because the CTs are connected in wye and the high-side currents lead the low-side currents by

30°, select the ∆2 position. This connection advances the low side phasors by 30° to match the

phasors from the high-side.

HIGH

LOW

Jumper Position:

WYE

2

On single-phase units, the zero-sequence currents must be canceled by connecting the low

side CTs in delta.

Step 4. Determine the relay current (I

R

):

I

R

=I

S

x Conversion Factor

Three-Phase Units Only: When using either

1 or

2 jumper positions, shown in Figure 2-4,

multiply the secondary current I

S

by the conversion factor (square root of three) just as if the

CTs were connected in delta. If the system CTs are connected in delta (either three-phase or

single-phase units), the same square root-of-three conversion factor must be applied.

HIGH

LOW

Step 5. Determine the spread ratio of the relay currents (largest/smallest) which must be less than the

4.45 capability of the BE1-87T:

Spread = 10.02/2.79 = 3.59

If the spread exceeds 4.45, consider changing CT ratios or use auxiliary CTs.

Step 6. Determine the Driving Input (DP) which we define as the input assigned to the smallest current

in Step 4.

DP=I

M

DP=HIGH (INPUT 1)

I

I

S

P

=

CT ratio

I

I

S

S

=

=

167.35

60

2.79

I

I

S

S

=
=

925.98

160

5.79

I
I

R
R

=
=

(2.

2

79) (1)

79

.

I
I

R
R

=
=

5

3

10

.

.

79

02

Advertising