See figure 4-34 for 3-phase connections.) – Basler Electric BE1-87T User Manual

Page 77

Advertising
background image

9171300990 Rev V

BE1-87T Installation

4-35

Figure 4-36. Application Example: Autotransformer With Tertiary Winding

(See Figure 4-34 for 3-phase connections.)

Specifications

High side

Tertiary

Low side

kV

345

13.2

138

MVA

200/250

40/50

200/250

CT Ratio

600/5 (MR)

600/5 (T)

3000/5

2000/5 (MR)

1200/5 (T)

CT Accuracy Class

C400

C800

C400

CT Resistance (ohms)

0.3

1.5

0.6

One-Way Lead Burden (ohms) 0.7

0.7

0.7

CT Connection (Three-Phase) WYE

WYE

WYE

NOTE

Three-phase is the most common application of the BE1-87T. Using single-

phase relays requires a Delta connection for the High side and Low side CTs

(IA-IB to match the tertiary connection in the example detailed in Figure 4-34).


Step 3. Three-Phase Units Only: Adjust the phase compensation jumpers on Analog Board #2, shown

in Figure 2-4 and Figure 4-27, (or use the procedure listed in Testing Three-Phase Units without

Changing Jumpers, in Section 5).

Because of the grounded winding in this example, as shown in Figure 4-35 and 4-34, the high-

side, and low-side zero-sequence currents must be canceled.

2 position is selected to align

the High side and Low side secondary current phasors with the tertiary phasors which lead by

30° in this example:

HIGH

TERTIARY

LOW

Jumper

Position:

2

WYE

2

Step 4. Determine the relay current (I

R

):

X

X

600/5MR

600/5T

3360 A (3 ∅)

3375 A (1 ∅)

13,280 A (3 ∅)

3000/5

2000/5MR

1200/5T

138 kV

8400 A (3 ∅)

9000 A (1 ∅)

345 kV

02-12-98

D240-004

BE1-87T

WYE (3)

WYE (3)

(12)

(12)

13.2

kV

WYE (3)

A

1

(12)

+

10% LTC (11)

HIGH

SIDE

TERTIARY

LOW SIDE

I

I

R

S

=

× Conversion Factor