Input (or tap) switch verification, Input (or tap) switch verification -15, Table 5-5. restraint pickup test: 1 a, 50 or 60 hz – Basler Electric BE1-87T User Manual

Page 111

Advertising
background image

9171300990 Rev V

BE1-87T Test Procedures

5-15

Step 8. If the relay has more than two inputs, reconnect the relay by substituting the Input 3 terminals

for the Input 2 terminals. Then repeat step 6 and 7 using the Input 2 values of Table 5-5 for

Input 3.

If there are more than three inputs (as in some single-phase units), continue substituting every

higher-numbered input for Input 2, each time comparing the input under test against Input 1 as

in Steps 6 and 7.

Step 9. Three-Phase Units Only: Repeat Steps 6, 7 and 8 for phases B and C. (Refer to Figures 5-1

through 5-4, as appropriate, for the terminal numbers of the phase B and C inputs of the relay

under test.)

Table 5-5. Restraint Pickup Test: 1 A, 50 or 60 Hz

Input 1, Tap = 2.0 Input 2, Tap = 3.8

Increasing Input 1 Decreasing Input 2

% Slope Amperes X Tap Amperes X Tap

Trip Amperes

Trip Amperes

15

0.4

1

0.76

1

0.540 ±0.052

0.494 ± 0.050

15

0.8

2

1.52

2

0.941 ±0.076

1.254 ± 0.095

15

1.2

3

2.28

3

1.412 ±0.105

1.938 ± 0.136

15

2.0

5

3.8

5

2.353 ±0.161

3.230 ± 0.214

25

0.4

1

0.76

1

0.540 ±0.052

0.494 ± 0.050

25

0.8

2

1.52

2

1.067 ±0.084

1.140 ± 0.088

25

1.2

3

2.28

3

1.600 ±0.116

1.710 ± 0.123

25

2.0

5

3.8

5

2.667 ± 0.180

2.850 ± 0.191

50

0.4

1

0.76

1

0.800 ± 0.068

0.380 ± 0.043

50

0.8

2

1.52

2

1.600 ± 0.116

0.760 ± 0.066

50

1.2

3

2.28

3

2.400 ± 0.164

1.140 ± 0.088

50

2.0

5

3.8

5

4.00 ± 0.260

1.900 ± 0.134

30

0.4

1

0.76

1

0.571 ± 0.054

0.494 ± 0.050

30

1.2

3

2.28

3

1.714 ± 0.123

1.596 ± 0.116

35

0.4

1

0.76

1

0.615 ± 0.057

0.494 ± 0.050

35

1.2

3

2.28

3

1.846 ± 0.131

1.482 ± 0.109

40

0.4

1

0.76

1

0.667 ± 0.060

0.456 ± 0.047

40

1.2

3

2.28

3

2.000 ± 0.140

1.368 ± 0.102

55

0.4

1

0.76

1

0.889 ± 0.073

0.342 ± 0.041

55

1.2

3

2.28

3

2.667 ± 0.180

1.026 ± 0.082

Input (or Tap) Switch Verification

Each input is scaled using a combination of two rotary switches. Verify the switches as follows.

Step 1. Determine the Sensing Input Type (the first digit of the Style Number shown on the front panel):

A

Single-phase, two inputs

B

Single-phase, three inputs

C

Single-phase, four inputs

D

Single-phase, five inputs

E

Three-phase, two inputs each phase

G

Three-phase, three inputs each phase