Basler Electric BE1-87T User Manual

Page 86

Advertising
background image

4-44

BE1-87T Installation

9171300990 Rev V

Step 7. Determine the Driving Input Tap (T

I

).

If both relay currents are between 2.0 and 8.9 amperes, the tap settings can be set equal to the

relay currents (to the nearest 0.1 ampere). However, choosing the 2.0 tap setting for the

minimum input will yield maximum sensitivity.

T

1

= 2.00

Step 8. Determine the desired Tap (T

D

) for Input 2:

Step 9. Select taps by rounding T

D

to the nearest tenth:

T

1

= 2.0

T

2

= 7.2

Step 10. Determine the CT mismatch (M

N

):

M

N

= 100

Current Ratio - Tap Ratio

the smaller of the above

I

I

T

T

Smaller

R2

=

-

R1

1
2

100

= 0 216

0 22 %

=

-

2.79

2.0

Smaller

100

or

.

.

=

-

0.2784 0.2778

0.2778

100

10.02

7.2

Step 11. Determine the total mismatch (M

T

):

M

T

= M

N

+ LTC

Add the maximum CT mismatch M

N

(based on the power transformer in the neutral tap

position) to the total permissible tap excursion from neutral. In this example, a

±

10 % load-tap

change (LTC) must be accommodated. Therefore:

M

T

=0.22 + 10 = 10.22%

T

T I

I

D

R

R

2

1

2
1

2.0 10.02

2.79

7

=

( )

=

= .18

(

)