Setting note 2 – Basler Electric BE1-87T User Manual

Page 130

Advertising
background image

A-2

BE1-87T Setting Notes

9171300990 Rev V

Setting Note 2

I

A

+I

B

+I

C

=0

I

A

=-(I

B

+I

C

)

V=I

A

R

W

+(I

A

-I

C

)(R

L

+R

R

)-(I

B

-I

A

)(R

L

+R

R

)

=I

A

(R

W

+R

L

+R

R

+R

L

+R

R

)-I

B

(R

L

+R

R

)-I

C

(R

L

+R

R

)

=I

A

(R

W

+2R

L

+2R

R

)-(I

B

+I

C

)(R

L

+R

R

)


Since I

A

=-(I

B

+I

C

)

V=I

A

(R

W

+3R

L

+3R

R

)

Where:


I

A

= 3-Phase fault current

R

R

= Relay burden

R

L

= Lead burden

R

W

= Winding burden

Figure A-2. CT Burden-Delta Connected CTs 3-Phase Fault

B

A

D2751-17

01-30-98

R

W

V

R

W

I

A

I

B

I

C

C

R

W

R

W

R

L

I

C

- I

B

R

L

I

A

- I

C

R

L

I

B

- I

A

R

R

R

R

R

R