Wye ∆2 – Basler Electric BE1-87T User Manual

Page 74

Advertising
background image

4-32

BE1-87T Installation

9171300990 Rev V

Figure 4-35. Three-Phase Connections, Autotransformer With Loaded Delta Tertiary


The transformer in the example shown in Figure 4-34 has a delta connection on the tertiary winding. The

currents in each winding of the delta are A, B, and C respectively as reflected from the wye or auto

connected winding. The delta connection of the transformer windings causes the current flowing in the

phase leads connected to the delta winding to be A-B, B-C and C-A respectively. The CT currents on the

wye or auto windings must be combined similarly to provide A-B, B-C and C-A to compensate. This is

shown in Figure 4-34 by selecting phase compensation jumper position ∆2 for these inputs. This also

provides zero sequence blocking for these inputs since this transformer configuration is a source of zero

sequence currents.