Response time verification, Response time verification -18, Table 5-8. timing, 1 a, 50 or 60 hz – Basler Electric BE1-87T User Manual

Page 114

Advertising
background image

5-18

BE1-87T Test Procedures

9171300990 Rev V

Response Time Verification

Step 1. Connect the relay as appropriate (refer to Figures 5-1 through 5-4).

Step 2. Set the RESTRAINED PICKUP LEVEL switch (phase A) to A (15%). Place all of the INPUT

switches on the

0.4 A tap position.

Step 3. Apply 0.4 A at 50 or 60 Hz, as appropriate for the style, to Input 1 (terminals 11 & 13 on both

single- and three-phase styles) and to Input 2 (terminals 12 & 13 on single-phase and terminals

15 & 18 on three-phase).

Step 4. Perform a restrained trip at 2 x Pickup by stepping the Input 2 current to 0.68 A. Note the time

interval between initiation of the simulated fault and the closure of the restrained output contact.

The trip time should be less than that shown in Table 5-8.

Step 5. Repeat Step 4 at

= 10 x Pickup. Note that, with Input 1 at 0.4 A, Input 2 current should be

stepped to 1.8 A. The trip time should be less than that shown in Table 5-8.

Step 6. Three-Phase Units Only: Repeat Steps 1 through 5 for Phases B and C.

Step 7. Place the UNRESTRAINED PICKUP LEVEL switch to the A setting (6 X TAP). Place all of the

INPUT switches to the 0.4 A tap position.

Step 8. With 0.0 A at Input 1 (terminals 11 & 13), apply 4.8 A (2 x Pickup) to Input 2 (terminals 15 & 18

on three-phase). Note the time interval between initiation of the simulated fault and the closure

of the unrestrained output contact. The interval should be less than that shown in Table 5-8.

Step 9. Repeat Steps 7 and 8 at 10 × Pickup. Note that, with Input 1 at 0.0 A, it will be necessary to

step the Input 2 current to 24 A for an unrestrained trip. The trip time should be less than that

shown in Table 5-8.

Step 10. Three-Phase Units Only: Repeat Steps 8 and 9 for phases B and C.

Table 5-8. Timing, 1 A, 50 or 60 Hz

Function

Differential Current

Option 1-0

Timing Maximum

Option 1-1

Timing Maximum

50 Hz

60 Hz

50 or 60 Hz

Restrained Trip

2 x Pickup

81 ms

70 ms

49 ms

Restrained Trip

10 x Pickup

73 ms

67 ms

37 ms

Unrestrained Trip

2 x Pickup

64 ms

52 ms

57 ms

Unrestrained Trip

10 x Pickup

32 ms

28 ms

10 ms

I