Setting note 4, Setting note 5, Slope margin – Basler Electric BE1-87T User Manual

Page 132: Sf 87t, 10 × i

Advertising
background image

A-4

BE1-87T Setting Notes

9171300990 Rev V

Setting Note 4

1) Find the maximum pu fault current for external faults (ie).
2) Assume that one of the input CTs saturates to 70%.
3) Set unrestraint pickup >.7 X IE.

Figure A-4. Unrestraint Tap Setting

Setting Note 5

Slope Margin

The slope formula accounts for an operating current bias due to magnetizing current in one winding. The

magnetizing current is assumed to be 4% of the OA rating. Step 20 is used to scale this magnetizing ratio

to the corresponding ratio of relay operate current: 4 x I

T

%.

The formula further assumes a conservative margin corresponding to an operation current of 23% of tap.

The actual margin varies with the tap settings, as given by the following equation:

(

)

Margin =

− × −

+ ×

35 4

3 35

I

M

S

T

T

The margin variations for different tap settings (I

T

) can be evaluated with this equation. The following plots

show the calculated slope and the resulting margin for M

T

varying from 1 to 11% and I

T

varying from 0.5 to

2 (plot shows

10 × I

T

).

S

F

87T

D2751-18

02-03-98

I

FH

I

FH

/R

CL

0.3I

FL

/R

CL

R

CL

-

+

I

OP

TRIP

UNRESTRAINT

MPU SETTING

T

H

T

L

0 3

. ×

×

I

R

T

FL

CC

L

I

R

T

FH

CH

H

×

R

CH

I

FL

D2751-19

03-12-98