4-34

BE1-87T Installation

9171300990 Rev V

Table 4-1. List of Variables

D

P

The driving input number, a procedural term designating the current input

terminal whose tap is the first selected. (The setting procedure is simplified if

the driving input is the input of least current, I

M

)

I

E

Maximum external fault current in multiples of tap (the larger of three-phase or

line-ground values)

I

D

Driving input relay current used for matching in amperes

I

F

The larger of I

F3

and I

FG

I

F3

Relay input current at the maximum external three-phase fault level in

secondary amperes

I

FG

Relay input current at the maximum external line-ground fault level in

secondary amperes

I

M

The input with the least minimum current

I

P

CT primary current in amperes

I

R

Relay input current in amperes

I

S

CT secondary current in amperes

I

T

Rated self-cooled current of the power transformer in multiples of tap

M

N

Current mismatch, with power transformer on its neutral tap

MR

Multiple rating CT, i.e., a tapped CT

M

T

Total mismatch, including the maximum transformer tap excursion

N

Total number of CT turns available

N

A

Number of CT turns in use

R

L

One-way lead resistance in ohms

R

W

CT winding resistance in ohms

R

R

Relay resistance in ohms

S

Restrained slope setting (from 15 to 60%)

S

F

Saturation factor, which equals V

B

/V

CE

T

Relay current tap (0.4 to 1.78 for 1 A CT, 2 to 8.9 for 5 A CT)

T

D

Desired tap, based on the current ratio

V

B

The larger of V

B3

or V

BG

V

B3

The CT burden voltage with I

F3

flowing

V

BG

The CT burden voltage with I

FG

flowing

V

C

Base accuracy class CT voltage rating

V

CE

Accuracy class CT effective voltage where not all turns are used, which equals

V

C

(N

A

/N)

x TAP

Unrestrained pickup setting, in multiples of tap (6 to 21)