5-20

BE1-87T Test Procedures

9171300990 Rev V

Step 7. For 50 Hz Units: Holding the 50 Hz current constant at tap value, add a 100 Hz (I

100

) current in

parallel with I

50

. Increase I

100

until the

REST. TRIP LED extinguishes. The inhibit percentage is

100

100

50

× I

I

at the point where the LED extinguishes.

Expected Values: 12±3% for single-phase

18±3% for three-phase

For 60 Hz Units: Holding the 60 Hz current constant at tap value, add a 120 Hz (I

120

) current in

parallel with I

60

. Increase I

120

until the

REST. TRIP LED extinguishes. The inhibit percentage is

100

120

60

× I

I

at the point where the LED extinguishes.

Expected Values: 12±3% for Single-Phase

18±3% for Three-Phase

Fifth-Harmonic Inhibit

Step 8. For 50 and 60 Hz Units: Apply tap value (1 pu) to Input 1. REST. TRIP LED should be

illuminated.

For Three- Phase Units: Return S2 to the NORMAL position.

Step 9. For 50 Hz Units: Holding the 50 Hz current constant at tap value, add a 250 Hz (I

250

) current in

parallel with I

50

. Increase I

250

until the

REST. TRIP LED extinguishes. The inhibit percentage is

100

250

50

× I

I

at the point where the LED extinguishes.

Expected Values: 35±3% for single-phase or three-phase units.

For 60 Hz Units: Holding the 60 Hz current constant at tap value, add a 300 Hz (I

300

) current in

parallel with I

60

. Increase I

300

until the

REST. TRIP LED extinguishes. The inhibit percentage is

100

300

60

× I

I

at the point where the LED extinguishes.

Expected Values: 35±3% for single-phase or three-phase units.

Testing Three-Phase Units without Changing Jumpers

The simplest way to test three-phase units using only two test currents is to set all jumpers to the

WYE

position. Then each comparison circuit is tested independently when the respective phase currents are

applied. This is not acceptable from two points of view:

Requires changing the relay settings (jumpers) from the in-service position.

Does not verify that the jumpers have been properly set.

It is possible to completely test the BE1-87T with the jumpers set to the in-service position and still use

only two input current sources. When the jumpers are in the positions shown in Table 5-9, the respective

current inputs are compared.