Installation Preparations

Requirements on Environment

The MSR 50 routers are designed for indoor applications. To ensure the normal operation and prolong

their service life, the following requirements for installation site must be met.

Requirements on Temperature/Humidity

To ensure the normal operation and prolong their service life, certain requirements on temperature and

humidity in the equipment room shall be met. If the relative humidity is too high, the insulation materials

in it will deteriorate easily or even lead to electric leakage. Sometimes this will result in change to the

mechanical performance of the materials and rusting of the metal components. If the relative humidity is

too low, the fastening screw will become loosen due to shrinkage of the isolation spacer. In an
environment with dry climate, static electricity may be produced, putting the CMOS of the router to risk.

High temperature is of the greatest risk: for it will significantly degrade the router’s reliability, speed up

aging process of the insulating materials, and shorten the service life of the router.
The requirements on the temperature and humidity for MSR 50 are shown in the following table:

Table 12 Temperature/humidity requirements in the equipment room

Temperature

Relative humidity (noncondensing)

0°C to 40°C (32°F to 104°F)

5% to 90%

Requirements on Cleanness

Dust is harmful to the safe operation of the Router. Dust on the chassis may result in static absorption, thus

causing poor contact of the metal connection components or points. Especially under the condition of

low indoor humidity, dust is easier to be absorbed.
The requirements on the dust concentration and diameter are shown in the following table:

Table 13 Limitation on dust content in equipment room

Diameter (μm)

0.5

1 3 5

Concentration (particle/m³)

1.4 × 107

7 × 105

2.4 × 105

1.3 × 105

Besides the dust specifications, the equipment room of the Router should also meet the rigorous

requirements for the content of salt, acid and sulfide. These harmful gases could accelerate the metal

erosion and aging process of some parts. The specific limits of these harmful gases as SO

2

, H

2

S, NO

2

,

NH

3

and CI

2

are given in the following table.