3

WIRING

23

Layout of control circuit terminals

21

22

23

9

10

25

26

27

33

18

19

20

11

12(G)

1

2

3

4

5

6

7

8

13

14

15

16

17

1.

indicates shielded wires and

indicates twisted-pair shielded wires.

2.

Either control circuit terminal 13 or 14 can be used. (For simultaneous inputs, the two
signals are added internally.)

3.

Control circuit terminal 15/33 of +15 V/-15 V has a maximum output current capacity of
20 mA.

4.

Multi-function analog output should be used for monitoring meters (e.g. output frequency
meter) and should not be used for feedback control system. Use analog monitor cards
(Model AO-12) for the control system, for a more accurate signal.

5.

When using a braking resistor unit, set the constant L3-01 to “0” (overvoltage prevention
level is “disabled”). If it is not changed, the motor may not stop within the set decel time.

6.

When using model ERF braking resistor (inverter-mounted type), set the constant L8-01
to “01” (braking resistor protection selection to “enabled”). If it is not changed, the brak-
ing resistor cannot be protected.

7.

When installing a DC reactor (optional for models of 15kW or below), remove the short-
circuit bar between ¨1 and ¨2 terminals and connect a DC reactor with the terminals.

8.

The models of 200V 30 to 75kW or 400V 55 to 160kW cannot be connected with DC pow-
er supply.

9.

Once external baseblock signal is turned ON, do not release until a motor stops.

NOTE

NOTE