Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 27

Advertising
background image

28

(h) Using Output Noise Filters

By installing a noise filter on the output side of the inverter, radio frequency interference
(RFI) and inductive noise are reduced.

M

MCCB

VS-686SS5

Power

Supply

Noise

Filter

RFI Noise

AM Radio

Inductive

Noise

Signal Line

Control

Device

Fig.

12

Using Output Noise Filter

Inductive noise: Noise coming on the signal line due to electromagnetic inductance can

cause malfunctioning of a control device.

RFI noise: Higher harmonics waves from the inverter or cable can interfere with radio

receiver.

(i) Countermeasures Against Inductive Noise

As described previously, a noise filter can be used to prevent inductive noise from generated
on the output side. Alternatively, cables can be routed through a grounded metal pipe to
prevent inductive noise. Keeping the metal pipe at least 30 cm away from the signal line
considerably reduces inductive noise.

M

MCCB

VS-686SS5

Power

Supply

Signal Line

Control

Device

Metal Pipe

30 cm min.

Fig.

13

Countermeasures Against Inductive Noise

(j) Countermeasures Against RFI Noise

RFI noise is generated form the inverter as well as from the input and output lines. To reduce
RFI noise, install noise filters on both input and output sides, and also install in a totally en-
closed steel box. The cable between the inverter and the motor should be as short as pos-
sible.

M

MCCB

VS-686SS5

Power

Supply

Metal Pipe

Noise

Filter

Noise

Filter

Steel Box

Fig.

14

Countermeasures Against RFI Noise

Advertising