Caution – Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 47

Advertising
background image

48

(c) Setting the Carrier Frequency

When changing the carrier frequency, contact your YASKAWA representative. To reduce
noise level by increasing the carrier frequency, it will be necessary to lower the rated current.

To reduce the motor noise during operation, change the setting of constant C6-02 (carrier
frequency selection). Note that this is not possible for all types of inverters. Table 14
shows whether or not noise reduction is possible by changing the setting of C6-02. Carri-
er frequency is set at 2 kHz at the factory.

The setting range of the carrier frequency is indicated in Table 14.

Table 14

Setting the Carrier Frequency

Inverter Model

CIMR-SSA

Setting Range of Carrier Frequency *

Remarks

20P4 to 2018

2, 4, 8, 12 kHz

40P4 to 4030

2, 4, 8, 12 kHz

High ← Magnetic noise → Low

2022 to 2075

2 4 8 kH

4037 to 4075

2, 4, 8 kHz

High ← Magnetic noise → Low

12 kHz cannot be set.

4110 to 4160

High ← Magnetic noise → Low

4185 to 4300

Only 2 kHz can be set.

*Carrier frequency lower limit is 2.0 kHz.

(d) Checking the Motor Speed Detection (For Flux Vector Control)

CAUTION

S

Verify that digital operator STOP LED is ON before checking motor speed detection.

S

Verify that nothing is caught on the shaft or coupling.

When the control method is flux vector, select motor speed display on the digital operator
display and check the followings as shown in Table 15.

S

Turn the motor shaft manually and verify that display of motor rotation direction
and polarity is correct.

S

Motor speed is displayed correctly.

Forward run: Clockwise as viewed from the opposite load side (standard setting).

See Fig. 21.

Forward Run

Load Side

Fig.

21

Motor Rotation Direction

NOTE

Advertising