APPENDIX 3 TYPICAL CONNECTION DIAGRAM

3.1

BRAKING RESISTOR UNIT

For Model CIMR-SSA20P4 to -SSA27P5 (200 V Class 0.4 to 7.5 kW),
Models CIMR-SSA40P4 to -SSA4015 (400 V Class 0.4 to 15 kW)

©

¨

1

DC Reactor

(Option) [

Overload Relay Trip Contact

Braking Resistor Unit ]

VS-686SS5

MCCB

3-Phase

Power Supply

200 to 230 V

50/60 Hz

or

380 to 460 V

50/60 Hz

R

MC

R (L1)

S

S (L2)

T

T (L3)

:

400/200 V

THRX OFF

ON

MC

SA

Overload Relay Trip Contact

of Braking Resistor Unit

1

2

MC

TRX

TRX

20 18

Fault

Contact

Forward Run/Stop

Reverse Run/Stop

Factory

Setting

External Fault

Fault Reset

Multi-step Speed Setting 1

(Master/Aux Change)

Multi-step Speed

Setting 2

Jog Reference

External Baseblock

Use sequencer to break

power supply side on

overload relay trip contact

of braking resistor unit.

¨

2

B1

B2

SA

SA

THRX

2 kΩ

2 kΩ

0 to +10 V

4 to 20 mA

P

0 to +10 V

P

0 V

P

External

Speed

Reference

Multi-function Open

Collector Output

48 V 50 mA or less

Multi-function

Output Common

27

Open Collector 2

(Speed Agree Signal

at Factory Setting)

26

Open Collector 1

(Zero Speed Signal at

Factory Setting)

25

Multi-function Contact Output

250 VAC 1 A or less

30 VDC 1A or less

(Signal during Running at Factory

Setting)

10

9

20

19

Fault Contact Output

250 VAC 1 A or less

30 VDC 1 A or less

18

+

AM

23

+

Multi-function Analog Output

-10 to +10V 2mA

(Output Current at Factory

Setting)

21

22

SM

Analog

Monitor 1

(12)

Multi-function Analog Output

-10 to +10 V 2mA

(Rotation Speed at Factory

Setting)

U (T1)

V (T2)
W (T3)

Motor

M

Ground (200V Class : 100Ω or less

400V Class : 10Ω or less)

:

The transformer is not necessary for 200V class.

1 Forward Run when

CLOSED

2 Reverse Run when

CLOSED

3

4

5

6

7

8

Multi-function

Contact Input

11

Sequence Common

Terminal (0V)

12

Shield Sheath

Connection Terminal

15 Speed Setting Power

Supply +15V 20mA

13 Master Speed Ref.

0 to 10V (20kΩ)

14 Master Speed Ref.

4 to 20mA (250Ω)

16 Multi-function Analog Input

0 to 10V (20kΩ)

0 V

33 Speed Setting Power Supply

-15V 20mA

17 (Aux Speed Ref. at

Factory Setting)

1

2

B

P

MC

Analog

Monitor 2

18

[

When installing a DC reactor (option), remove the common bar between ¨1 and ¨2 terminals

(provided as standard) and connect a DC reactor with the terminals.

]

When using the braking resistor unit, set constant L3-01 to “0” (overvoltage prevention selection

is disabled). If it is not changed, the inverter may not stop within set decel time.