3 wiring the main circuit, Warning, Caution – Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 23

Advertising
background image

24

3.3

WIRING THE MAIN CIRCUIT

WARNING

S

Make sure to ground the ground terminal

.

(Ground resistance 200V class: 100Ω or less, 400V class: 10Ω or less)
Failure to observe this warning can result in an electric shock or a fire.

CAUTION

S

Never connect the AC main circuit power supply to output terminals U, V and W.

The inverter will be damaged and invalidate the guarantee.

S

(Standard connection)

Be sure to connect the motor leads to the correct output terminals:
Motor lead U to output terminal U,
Motor lead V to output terminal V, and
Motor lead W to output terminal W.
Failure to observe this caution may cause the motor to run unusual way such as in reverse.

S

With the standard connection for the output terminals, the motor rotates counterclock-

wise as viewed from the load side in a forward operation. To rotate the motor clockwise
in a forward operation, connect the output terminals as refered in Appendix 6.

(1) Wiring Precautions for Main Circuit Input

(a) Installation of Molded-case Circuit Breaker (MCCB)

Make sure to connect MCCBs or fuses between the AC main circuit power supply and
VS-686SS5 input terminals R, S and T to protect wiring.

(b) Installation of Ground Fault Interrupter

When connecting a ground fault interrupter to input terminals R, S and T, select one that
is not affected by high frequency.

Examples: NV series by Mitsubishi Electric Co., Ltd. (manufactured in or after1988),

EG, SG series by Fuji Electric Co., Ltd. (manufactured in or after 1984)