6 modified constants mode – Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 63

Advertising
background image

64

5.6

MODIFIED CONSTANTS MODE

Compares the constant values preset at the factory with the values changed by the user, and displays
the constants changed from the preset constants automatically. In this mode, constants can be read;
in addition, they can also be set or changed.

[Example]

Read the constants C1-01 (acceleration time 1) and E1-01 (input voltage) when the factory settings
have been changed. In addition, change the setting of E1-01 (input voltage) from 220V to 230V
in this mode.

Table 28

Typical Operation in Modified Constants Mode

Step

Description

Key Sequence

Digital Operator Display

Remarks

Power ON

1

Switch to REMOTE mode.

LOCAL

REMOTE

G

REMOTE LED ON

2

Select modified constants mode.

RESET

DRIVE

PRGM

DRIVE LE

D blinks.

Modified constants mode can be ac-
cessed from drive mode by depress-
ing [RESET] and [DRIVE/PRGM]
keys simultaneously. Verify that
DRIVE LED is blinking.

3

Verify the set value.

DATA

ENTER

4

Return to constant No. display.

DSPL

5

Display the next-to-be-changed
constant.

6

Verify the set value.

DATA

ENTER

G

7

Change the value.

RESET

G

8

Write-in the value.

DATA

ENTER

Displays for 0.5 seconds.

9

Displays the set value.

G

10

Return to constant No. display.

DSPL

11

Return to drive mode.

DRIVE

PRGM

G