APPENDIX 5 ERROR PROCESSING IN PG ZERO-PULSE

ADJUSTMENT

91

Error processing during PG Zero-
pulse Adjustment

First error?

Yes

Is PG zero-pulse

adjusted at motor only?

Contact your YASKAWA
representative.

No

Is the motor vibrating?
Is STO displayed?

Disconnect motor from ma-
chine, and readjust PG zero-
pulse.

No

Reduce values of ASR gain 1
(C5-01) and ASR P gain at start
(C5-07) by 2/3, and then readjust
PG zero-pulse.

Yes

Yes

Did Er-18 occur?

Contact your YASKAWA
representative.

(Er-10 not included)

Are settings of motor
constants correct?

Yes

Refer to 4.3 (3) Setting and
Verification before Operation to
confirm settings of motor
constants, and then readjust PG
zero-pulse.

No

No

No

Yes

Cause 1: ASR P gain at start (C5-7) is too small.

Corrective action: Increase the ASR P gain at start 1.5 times.

Cause 2: Motor wiring or rotation direction of PG is incorrect.

Corrective action: Refer to 4.3 (3) (d) Checking the Motor Speed

Detection.

Cause 3: PG constant (F1-01) is incorrect.

Corrective action: Correct set value. After removing cause,

readjust PG zero-pulse.

Cause 4: Set value for operation selection for setting of E1-08 or

less (b1-05) is 30 min

-1

or more.

Corrective action: After setting the min. speed to 0 and adjusting

the PG zero-pulse, reset the min. speed.

Note: If the acceleration/deceleration times (C1-01 and C1-02) are set to values other than their

initial settings, change them back to their initial values and then adjust the PG zero-pulse.

Fig. A-1 Error Processing in PG Zero-pulse Adjustment