Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 77

Advertising
background image

78

For models CIMR-SSA2018, -SSA2022 (200 V Class 18.5, 22 kW)

(ℓ

2

)

3-Phase

Power Supply

200 to 230 V

50/60 Hz

R

S

T

M

r (ℓ

1

)

Cooling Fan

(12)

Short-circuit Bar

(Provided as

Standard)

Ground (100Ω or less)

Braking Unit

(Option)

P

B

Braking Resistor

Unit (Option):

1

2

Overload Relay Trip Contact

Level

Detection

3

4

U

V

W

Motor

M

¨

1

MCCB

R

MC

S

T

¨

2

©

¨

3

Braking Unit

3

4

THRX

OFF

ON

MC

SA

Overload Relay Trip Contact

of Braking Resistor Unit

1

2

MC

TRX

TRX

20 18

Fault

Contact

SA

SA

THRX

MC

Forward Run/Stop

Reverse Run/Stop

Factory

Setting

External Fault

Fault Reset

Multi-step Speed Setting 1

(Master/Aux Change)

Multi-step Speed

Setting 2

Jog Reference

External Baseblock

2 kΩ

2 kΩ

0 to +10 V

4 to 20 mA

P

0 to +10 V

P

0 V

P

17 (Aux Speed Ref. at

Factory Setting)

15 Speed Setting Power

Supply +15V 20mA

3

4

5

6

7

8

Analog

Monitor 1

11

0 V

1 Forward Run when

CLOSED

2 Reverse Run when

CLOSED

Multi-function

Contact Input

Sequence Common

Terminal (0V)

12

Shield Sheath

Connection Terminal

13 Master Speed Ref.

0 to 10V (20kΩ)

14 Master Speed Ref.

4 to 20mA (250Ω)

16 Multi-function Analog Input

0 to 10V (20kΩ)

33 Speed Setting Power Supply

-15V 20mA

21

22

23

+

AM

+

Multi-function Analog Output

-10 to +10V 2mA

(Output Current at Factory

Setting)

SM

Multi-function Analog Output

−10 to +10 V 2mA

(Rotation Speed at Factory

Setting)

Multi-function Open

Collector Output

48 V 50 mA or less

Multi-function

Output Common

27

Open Collector 2

(Speed Agree Signal

at Factory Setting)

26

Open Collector 1

(Zero Speed Signal at

Factory Setting)

25

Multi-function Contact Output

250 VAC 1 A or less

30 VDC 1A or less

(Signal during Running at Factory

Setting)

10

9

20

19

Fault Contact Output

250 VAC 1 A or less

30 VDC 1 A or less

18

Analog

Monitor 2

:

When using the braking resistor unit, set constant L3-01 to “0” (overvoltage prevention selection

disabled). If it is not changed, the inverter may not stop within set decel time.

Use sequencer to break

power supply side on

overload relay trip contact

of braking resistor unit.

VS-686SS5

¨

¨

0

©

0

©

External

Speed

Reference

18

20