5.1 Startup Sequence and Basic Operation

5.1.1 DIP Switch Settings

5-2

5.1 Startup Sequence and Basic Operation

This section describes the MP2300S startup sequence and basic operation together with the DIP switch settings, self-
diagnosis at startup, and LED indicator patterns.

5.1.1 DIP Switch Settings

Set the DIP switch (SW1) on the Basic Module to control operations of the startup sequence. The six switches are pro-
vided on the DIP switch (SW1) on the Basic Module as shown in the following figure. The following table lists the
functions of six switches.

No.

Switch

Name

Status

Operating Mode

Default
Setting

Remarks

S1-6 STOP

ON

User program stops

OFF

Set to ON to stop user program operation.

OFF

User program operation

S1-5 SUP

ON

System load

OFF

If set to ON, starts up in the mode that can renew the version
of the firmware.

OFF

Normal operation

S1-4 INIT

ON

Memory clear

OFF

Set to ON to clear memory.
Programs stored in flash memory will be run when Memory
Clear is set to OFF.
S and M registers are cleared to all zeros.

OFF

Normal operation

S1-3 CNFG

ON

Self-configuration mode

OFF

Set to ON for self-configuration of connected devices.

OFF

Normal operation

S1-2 MON

ON

System use

OFF

Always set to OFF.

OFF

Normal operation

S1-1 TEST

ON

System use
Adjusted before
Shipment

OFF

Always set to OFF.

OFF

Normal operation

SW

TEST

MON

CNFG

INT

SUP

STOP

NO