2.3 Option Module

2.3.1 Option Module Overview List

2-63

Specifications and Functions

Input/Out-
put Module

LIO-01/
LIO-02
Module

Digital I/O and pulse counter functions.
As a digital I/O function, equipped with 16 digital inputs (DI), 16 digital
outputs (DO) (LIO-01: sink output, LIO-02: source output). As a pulse
counter function, one pulse input (PI). As for when to input/output for
digital I/O and pulse counter functions, input/output for each MP2200
high-speed (High)/ low-speed (Low) scan is carried out at a constant
cycle.

Machine Controller MP2300S
Basic Module User’s Manual

(manual number:
SIEP C880700 03)

LIO-04/
LIO-05
Module

As a digital I/O function, equipped with 32 digital inputs (DI), and 32
digital outputs (DO) (LIO-04: sink output, LIO-05: source output).

LIO-06
Module

As a digital I/O function, equipped with 8 digital inputs (DI), 8 digital
outputs (DO), one analog input channel, one analog output channel, and
one pulse counter input channel.

DO-01
Module

As a digital output function, equipped with 64 digital outputs (DO) (sink
output).

AI-01 Module

8 channel analogue input module. For the input, capable of selecting
from three options: -10V to +10V, 0V to +10V, or 0 to 20 mA.

Machine Controller MP2000
Series I/O Module User’s Manual

(manual number:
SIEP C880700 34)

AO-01
Module

4 channel analogue output module. For the output, select one from two
options: -10V to +10V, or 0V to +10V.

CNTR-01
Module

2 channel reversible counter module. 5 V differential/ 12 V input is
optional, and phase-A or -B/ sign/ add-subtract method is optional.

Machine Controller MP2000
Series Counter Module CNTR-01
User’s Manual
(manual number:
SIEP C880700 27)

Communi-
cation
Module

218IF-01
Module

Equipped with serial interface (RS-232C) and Ethernet interface. Allows
you to connect to a personal computer, HMI equipment, or controller by
other makers via PORT or 10Base-T connector.

Machine Controller MP2000
Series Communication Module
User’s Manual
(manual number:
SIEP C880700 04)

218IF-02
Module

Equipped with serial interface (RS-232C) and Ethernet interface. Allows
you to connect to a personal computer, HMI equipment, or controller by
other makers via PORT or 10Base-T connector.

217IF-01
Module

Equipped with serial interfaces (RS-232C and RS422/485). Allows you
to connect to a personal computer, HMI equipment, or controller by other
makers via PORT or RS422/485 connector.

260IF-01
Module

Equipped with serial interface (RS-232C) and DeviceNet interface.
Allows you to connect to a controller by other makers via DeviceNet
connector. Also, allows you to connect to a personal computer or HMI
equipment by other makers via the PORT connector.

261IF-01
Module

Equipped with serial interface (RS-232C) and PROFIBUS interface.
Allows you to connect to a controller by other makers via the PROFI-
BUS connector. Also, allows you to connect to a personal computer or
HMI equipment by other makers via the PORT connector.

215AIF-01
Module

MPLINK and CP-215 specifications.
MPLINK specification is equipped with one line of our original real-time
core network interface MPLINK transmission and a serial interface (RS-
232C).
CP-215 specification is equipped with one line of our original real-time
core network interface CP-215 transmission and a serial interface (RS-
232C).

262IF-01
Module

Equipped with an FL-net interface. Allows you to connect to a FA con-
troller, a personal computer, or HMI equipment via 100Base-TX/10Base-
T connector.

Machine Controller MP2000
Series 262IF-01 FL-net Commu-
nication Module User's Manual
(manual number:
SIEP C880700 36)

263IF-01
Module

Equipped with an EtherNet/IP interface. Allows you to connect a per-
sonal computer or equipment that supports EtherNet/IP communication
protocol.

Machine Controller MP2000
Series 263IF-01 EtherNet/IP
Communication Module User's
Manual (manual number:
SIEP C880700 39)

(cont’d)

Classification

Option

Module Name

Module Overview

Reference Manual

Advertising