6.3 Communication with Touch Panel

6.3.1 When the MP2300S Acts as Slave (automatic receive function is used)

6-73

Built-in Ethernet Communications

[ b ] Screen Creation Example

1.

Create a base screen.

2.

Select Data Indicator from the toolbar to paste it on the screen.

3.

Double-click the Data Indicator pasted on the screen.

4.

Set as follows in the detailed setting screen of Data Indicator and click OK.

„

Relationship between GP-Pro EX address display and MP2300S register

Table 6.21 Data Indicator Detailed Setting

Display Data

Numeric display

Monitor Word Address

GMW00100

Device

GP-Pro EX Address Display

MP2300S Register

Coil (bit)

GMB††††††

MB††††††

Coil (word)

GMW†††††

MW†††††

Input Relay (bit)

GIB†††††

IB†††††

Input Relay (word)

GIW††††

IW††††

GP-Pro EX Screen

Paste

12345

GP-Pro EX Screen

Double-click

12345