5.2 User Programs

5.2.2 Motion Programs

5-15

Outline of Motion Control Systems

[ b ] Control Signal

Program control signals (e.g., program operation start requests and program stop requests) need to be entered to exe-
cute the motion program.
The following types of signals for controlling motion programs are available.

* 1. System work number setting

Œ

When a motion program is registered in M-EXECUTOR:
Unable to designate it. The same system work number as No. defined in the system is used.

Œ

When a motion program is invoked by a MSEE command from a ladder program:
OFF: A system work automatically retrieved by system is used. The system work number may differ in each

case.

ON: A work with the designated system work number is used.

However, when a work occupied by M-EXECUTOR is designated, “BitE: Error without a system work” is
reported to the status.

* 2. Override setting for interpolation

OFF: 100% fixed at an override for interpolation
ON: Depends on the designated override for interpolation.

Use signals conforming to the above signal types when writing ladder programs.

Note: Motion programs are executed if the program operation start request signal is ON when the power is

turned ON.

Table 5.2 Control Signals

Bit No.

Signal Name

Signal Type

0

Program operation start request

Differential or NO contact input

1

Program pause request

NO contact

2

Program stop request

NO contact

3

Program single block mode selection

NO contact

4

Program single block start request

Differential or NO contact input

5

Alarm reset request

NO contact

6

Program continuous operation start request

Differential or NO contact input

7

(Reserved)

8

Skip 1 information

NO contact

9

Skip 2 information

NO contact

A

(Reserved)

B

(Reserved)

C

(Reserved)

D

System work number setting

*1

NO contact

E

Override setting for interpolation

*2

NO contact

F

(reserved)