6.2 Communication with Other MP Series

6.2.3 When the MP2300S Acts as Master (I/O message communication function is used)

6-42

„

How to set up transmission parameters

c Set IP Address (“192.168.001.001”, for example).
d Click Edit, and then click Local Station: TCP/IP Setting in the Engineering Manager Window.
e Set Subnet Mask (“255.255.255.000”, for example).
f Set Gateway IP Address (“000.000.000.000”, for example).

„

Caution

Set up a unique IP address in the network.
For the IP address, check with your network administrator.

3.

Set connection parameters.

„

How to set up in the CP-218 Connection Parameter Window with connection numbers 05, 06

c Set Local Port (the port number “10005, 10006” used in the MP2300 side, for example).
d Set Node IP Address (the IP address “192.168.001.001” configured in the MP2300S side, for example).
e Set Node Port (the port number “10005, 10006” configured in the MP2300S side, for example).
f Select Connect Type (TCP, for example).
g Select Extended MEMOBUS for Protocol Type.
h Select Code (BIN, for example).

„

Caution

When any transmission or connection parameter is changed, the change will be reflected after FLASH has been saved and the
power supply is turned ON again.