Intrusion overview, Overview - intrusion zones – GE v6 User Manual

Page 188

Advertising
background image

Secure Perfect 6.1.1 User Manual

186

Intrusion Overview

Reference Topics:

Arm/Disarm an Intrusion Zone

Intrusion Zone Form

Activity Monitor Form

About Intrusion Options
Intrusion functionality provides the ability to define local intrusion zones per micro that consist of:

Readers

Alarms

Arm/disarm input point Intrusion DI

Arm/disarm output point DO

The defined intrusion zones have the ability to be armed and disarmed through access control by using a
card and keypad reader, DI, or manual control.
The intended application is suited for arming and disarming intrusion zones from outside of the monitored
and secured areas. Based on Secure Perfect system architecture, it is not our intent to fully emulate
traditional Burg/Intrusion panel functions but to provide similar functionality for less stringent
Burg/intrusion requirements that can be taken on natively within the access control system. Additionally,
the system provides increased value by allowing cross-system functionality between the Secure Perfect
micro and vendor-independent Burg/Intrusion panels.
Arm/Disarm Intrusion Point - Digital Input Form

An Intrusion DI Type has been added to the drop-down list on the Digital Input Form, Digital
Input tab.

When the Arm/Disarm Intrusion point is set/active (Armed), the associated zone is armed by
placing all readers offline, all alarm points monitored on, and the arm/disarm DO goes active.

When the Arm/Disarm Intrusion DI is reset/not active (Disarmed), the associated zone is
disarmed by placing all readers online, all alarm points monitored off (unless on a schedule),
and the arm/disarm DO goes inactive.

Intrusion Zone – Intrusion Zone Form
The Intrusion Zone Form is required for creating a relation between readers, alarm inputs, the
Arm/Disarm Intrusion point, and the arm/disarm DO.

1. An Intrusion Zone is defined with a description and

facility

assignment.

2. A micro selection is required to establish the zone source and its intrusion points.
3. The Intrusion Zone tab provides for the assignment of the following intrusion zone components:

arm/disarm DO, arm/disarm Intrusion DI, readers, and alarms.

Arm/Disarm Intrusion DI: This is a single record selection from a drop-down list filtered by
active facility that consists of all available Arm/Disarm Intrusion points for the micro. Only the
Dis that have not been assigned will be available.

Alarm Points: This is a multi-record selection from an assignment dialog filtered by active
facility that consists of available micro alarm points not already assigned to a zone. (24/7 4-
State Supervision rules apply regardless of the Armed/Disarmed state of the zone.)

Readers: This is a multi-record selection from an assignment dialog filtered by active facility
that consists of available readers not already assigned to a zone. (Readers must be active
and nonelevator type.)

A zone can be configured to contain the following:

An Arm/Disarm Intrusion Point with Alarm Points only and no Readers.
An Arm/Disarm Intrusion Point with Readers only and no Alarm Points
Alarm Points and Readers only with no Arm/Disarm Intrusion Point.
Readers only.

An arm/disarm DO can be assigned for any of these.

4. A Status tab provides the ability to request status of the zone and each of its associated points, as

follows.

Zone: Armed or Disarmed

Advertising